HVAC Maintenance Checklist
Quarterly preventive maintenance workflow for a manufacturing facility's rooftop and air-handling HVAC equipment. Run by the maintenance technician with sign-off by the maintenance lead; covers LOTO, AHU service, refrigerant circuit, ductwork, heating, and CMMS closeout.
Pre-PM Setup and Lockout/Tagout
-
Pull the CMMS work order and unit history
Open the PM work order in the CMMS (Fiix, eMaint, Limble, MaintainX) and review the prior visit's notes — recurring issues, deferred items, and any open follow-ups from the last quarter. Note the unit tag, model, and refrigerant type before walking out to the equipment.
-
Apply LOTO per the unit-specific procedure
Follow the equipment-specific LOTO procedure per 29 CFR 1910.147 — disconnect at the unit, apply your personal lock and tag, and verify zero energy by attempting a start. A skipped LOTO during blower or burner service is the OSHA Top-10 finding most likely to end careers.
-
Stage filters, belts, and gauge manifold
Pull replacement filters at the MERV rating specified for this unit, the belt size from the nameplate, and the refrigerant-specific gauge manifold (R-410A vs. R-22 vs. R-32 — never share manifolds across refrigerants).
Air Handling Unit Service
-
Replace return-air filters to MERV spec
Match the MERV rating on the spec sheet — over-spec'ing the filter restricts airflow and trips high static alarms on the BAS. Note arrow direction and seat the filter against the gasket, not just into the rack.
-
Clean the blower wheel and housing
Remove buildup from the blower wheel blades — a fingernail of dust per blade drops CFM measurably and unbalances the wheel. Inspect the housing for corrosion at the drain pan seam.
-
Check belt tension and sheave alignment
Use a tension gauge to the belt manufacturer's spec — finger-deflection is not a measurement. Lay a straightedge across both sheaves to verify alignment; misalignment shortens belt life by half and burns bearings.
-
Torque electrical lugs and inspect the contactor
Torque each lug to the manufacturer's spec on the inside of the panel door. Look for pitting on the contactor points — pitted contacts cause single-phasing and burn motors. Replace the contactor if points are pitted past a credit-card thickness.
-
Test the thermostat and BAS control response
Force a setpoint change at the BAS or stat and verify the unit responds — heating call, cooling call, fan-only. Note any drift between commanded and measured temperature greater than 2°F.
Refrigerant Circuit Service
-
Inspect refrigerant lines for oil traces
Walk the suction and liquid lines from the compressor to the indoor coil. Oil staining at flare fittings, brazed joints, or schrader cores is the field signature of a slow leak — confirm with an electronic detector or bubble solution before charging.
-
Record suction and discharge pressures
Connect the manifold and let pressures stabilize before reading. Record both readings against the saturation chart for the unit's refrigerant; pressures outside the manufacturer's envelope point to undercharge, overcharge, or a metering-device fault before they cause a compressor failure.
Collects paragraph -
Confirm whether a refrigerant leak was found
Based on the line inspection and pressure readings, declare whether a leak is present. EPA Section 608 leak-rate thresholds for commercial refrigeration begin at 35% annual leak rate — appliances over the threshold trigger mandatory repair within 30 days.
Collects list -
Log refrigerant recovery and repair plan
EPA Section 608 requires a certified technician to recover refrigerant before opening the system, and to log recovered/added quantities in the unit's service record. Schedule the leak repair within the regulatory window and notify the maintenance lead before any topping-off.
-
Wash condenser and evaporator coils
Use coil cleaner rated for the fin material — aluminum-fin condensers reject acidic cleaners, copper coils tolerate them. Rinse from the inside out so debris exits the way it entered.
-
Verify TXV superheat within spec
Measure superheat at the suction line near the TXV bulb; compare to the manufacturer's target (typically 8–12°F). Persistent high superheat with normal pressures usually means a sticking valve or a lost bulb charge, not a refrigerant problem.
Ventilation and Ductwork
-
Inspect duct seams and external insulation
Check transverse joints and longitudinal seams for separation, mastic failure, or open screws. Leaks at the supply trunk near the unit are responsible for the bulk of measured duct losses — fix these before chasing branch leaks.
-
Clean supply diffusers and return grilles
-
Cycle fire and balancing dampers
Stroke each accessible damper through full travel and confirm the actuator returns to commanded position. Stuck fire dampers are an NFPA 80 finding at the next fire-marshal inspection; document any that won't reset.
-
Verify airflow against design CFM
Take a hood reading at two or three diffusers and compare against the balance report. Drops of more than 10% from the commissioning baseline usually trace back to filter loading, a slipping belt, or a closed damper.
Heating System Check
-
Inspect the heat exchanger for cracks
Use a borescope on each cell — daylight inspection misses hairline cracks that vent CO into the supply air. A cracked exchanger is a life-safety condition: the unit gets red-tagged immediately, no exceptions for production schedule.
Collects list -
Red-tag the unit and notify the maintenance lead
Lock the unit out of service, apply a red Do-Not-Operate tag, and call the maintenance lead before leaving the roof. A cracked exchanger that runs another shift is how facility CO incidents become OSHA recordables.
-
Test ignition sequence and flame signal
Cycle the heat call and watch the ignition sequence: pre-purge, igniter glow or spark, gas valve open, flame proven, blower on. Measure the flame-rectification microamps against the board's minimum — a weak signal predicts nuisance lockouts on the coldest morning.
-
Run combustion analysis and verify CO/CO2
Use a calibrated combustion analyzer at the flue. Record O2, CO2, CO, and stack temperature; compare against the burner manufacturer's targets. CO above 100 ppm air-free is a stop-and-fix condition, not a tweak-the-air-shutter condition.
Closeout and Documentation
-
Remove LOTO and verify safe restart
Walk the panel and confirm covers are reinstalled and screws torqued before pulling locks. Restore power, watch the first start cycle, and listen for unusual bearing or contactor noise before leaving the equipment.
-
Close the work order with technician sign-off
Upload field photos of the filter change, coil condition, and combustion-analyzer readout. Attach the technician signature to close the CMMS work order; the maintenance lead reviews the sign-off and any flagged follow-ups before the WO closes for the quarter.
Collects signature Collects paragraph Collects file
Use this template
Copy it to your account, customize the steps, and run it with your team in minutes.
Browse hundreds of free templates across every team and industry.
Back to template libraryRun HVAC Maintenance Checklist with your team
Customize the steps, assign roles, set a schedule, and keep a complete record for every run.